Article directory
Search by method, process, Grade A–D, or regulatory term. Select a subject area to narrow the library.
Quick comparison: classification particle limits
EU GMP Annex 1 Table 1 sets classification thresholds. These limits are not interchangeable with the routine monitoring values in Table 5.
| Grade | ≥0.5 µm at rest | ≥0.5 µm operating | ≥5 µm at rest | ≥5 µm operating |
|---|---|---|---|---|
| A | 3,520 | 3,520 | Not specified* | Not specified* |
| B | 3,520 | 352,000 | Not specified* | 2,930 |
| C | 352,000 | 3,520,000 | 2,930 | 29,300 |
| D | 3,520,000 | Risk-based** | 29,300 | Risk-based** |
* Not specified by default; the CCS or historical trends may justify classification at ≥5 µm. ** Grade D operating limits are manufacturer-defined from risk assessment and applicable routine data. Annex 1 §4.27 / Table 1.
Process-risk grade navigator
Educational tool only. A GMP grade cannot be assigned solely from one dropdown; the CCS, isolator design, sterile exposure and process risk must be assessed.
Qualification readiness checklist
Save locally in your browser and export a CSV summary for project review. The checklist is guidance, not a controlled qualification record.
Official standards and existing technical files
- European Commission — EU GMP Annex 1 (2022) — Paragraphs 2.1–2.6, 4.4–4.32, 7.1–7.18, 9.1–9.32 and Tables 1, 2, 5, 6; checked 2026-11-06
- ISO 14644-1:2015 — Air cleanliness by particle concentration — Published ISO overview; full copyrighted text not reproduced; checked 2026-11-06
- European Commission — EudraLex Volume 4 regulatory portal — Annex 1 version cross-check
Existing Pharmatalks Google Drive materials
- Pharmatalks — Cleanroom Qualification SOP (Drive PDF)
- Pharmatalks — HVAC / Cleanroom Complete Guide (Drive PDF)
- Pharmatalks — GMP for Sterile Products (Drive PDF)
- Existing Pharmatalks cleanroom particle-classification HTML (Drive)
- Existing Pharmatalks airflow visualization guide (Drive HTML)
- Existing Pharmatalks microbiological air-sampling guide (Drive HTML)
These are verified file references in the connected Drive. They may not be publicly readable. No permission changes have been made.